Dissertation > Excellent graduate degree dissertation topics show
Research on the Cooling Systeml Based on the Variable Primary Flow in Air-conditioning Systems
Author: MaoLin
Tutor: ZhengQingHong
School: Xi'an University of Architecture and Technology
Course: Heating,Gas Supply, Ventilation and Air Conditioning Engineering
Keywords: variable flow system cooling tower frequency conversion COP energy-saving
CLC: TU831.3
Type: Master's thesis
Year: 2009
Downloads: 172
Quote: 0
Read: Download Dissertation
Abstract
|
The central conditioner cooling water system were made of the heat-exchange equipment,cooling water pump and cooling tower.The cooling water system would lead to waste of electrical energy and water resource due to the unreasonable design or unsuitable operation.There is big space to save energy.To reduce the central conditioner cooling water system energy consumption,this article analyze the influence factors about energy consumption in every section through calculating,based on actual project and cooling water pump frequency energy saving condition.Take an office building in xi’an for example,this article get refrigerating parameter and parameter of the energy consumption in condition of changing cooling water pump frequency,cooling tower fan amounts and refrigerating parameters of refrigerating unit seperately,as well as recording outdoor weather parameters in complete operation cycle.Based on enthalpy potential method,this article gives calculating about the capacity of each heat exchanger of cooling tower considering outdoor weather parameters in different moment and get the capacity of each heat exchanger of cooling tower.From the result which come from calculating water pump energy consumption in different frequency,we know water pump energy consumption will reduce 23%if the frequency below 5Hz.Though analyzing experiment datas,we get connecting curves between COP,heat exchange efficiency of the cooling tower and system energy consumption under different controls by calculating refrigerating output, water pump performance and the cooling tower model of the heat interchanger.From the connecting curve,we know that:COP have the same change endency of raising in variable flow cooling water system and constant flow cooling water system,but compared to constant flow cooling water system,variable flow cooling water system COP is lower,so in the system which cooling water pump energy consumption take bigger proportion,variable flow cooling water system will consume less energy;the range of cooling tower circulating water is from 50%to 100%.corresponding to that the range of refrigeration for supply is from 73%to 100%,the cooling capability of cooling tower will go down along with circulating water dropping;When Rate of load condensate is below 50%,because of the power of water pump is small,variable flow cooling water system energy consumption and energy consumption for refrigerator are the same,enerny saving effect will be obvious,to reach 25%.
|
Related Dissertations
- Several Problems of Energy Saving Operation in Air Conditioning System of Large Scale Public Buildings,TU831.6
- Research on University’s Energy Saving System Facing the Construction of Green University,G647
- Applied Research of Emulsified Fuel on S195 Diesel Engine,TE626.24
- A Research and Development for Single Chip Micyoco AVR Usage,TP368.12
- Location Assisted Wi-Fi Discovery on Mobile Devices for Energy Saving,TN929.53
- Research on Evaluation of Coal Enterprise Energy-Saving Mechanism,F206
- Study on Green Finance Promotes Industrial Restructuring,F832;F205
- The Research and Implementation of Energy-efficient RAID,TP333
- Study on the Energy Efficiency Prediction Model of the Plant of Central Air-conditioning System,TU831.4
- Sustainable Construction Design Analysis in Macau,TU201.5
- The Research and Application of Fuzzy Control in HVAC and Room System,TB657.2
- Horizontal elliptical tube under the action of the water film heat transfer performance of,TK124
- Under the Condition of Gansu Province Regional Highway Toll and Affiliated Facilities Construction,U417.7
- Study of Heat Transfer Enhancement about Semiconductor Refrigerating System,TB657.5
- The Study of the Electromyography Activities of Trunk Muscle During Load and Unload in Different Static Postures,R687.3
- Study on the Contamination Status of Legionella in Central Air Conditioning Cooling Tower Water, Transmission and Human Infection,R126.4
- Frost resistance of concrete cooling tower,TU528
- Transportation Optimization for Special Equipment in Electric Power System,TM621
- Composite ground source heat pump auxiliary cooling cooling tower,TK523
- The Study of New Type Fuel Saving Engline with Wireless Remotecontrol Technique,TK40
- Declines of Lateral Balance in Old People and Effects of Regular Tai Chi Exercise on the Declines,G852.11
CLC: > Industrial Technology > Building Science > Housing construction equipment > Air-conditioning, heating, ventilation,and its equipment > Air-conditioning > Air-conditioning systems