The Study of Lightning Protection Performance for 500kV Parallel-Four-Circuit-Transmission-Lines

Author: HuangYeTong
Tutor: ZhangYongJun;FengFuCheng
School: South China University of Technology
Course: Electrical Engineering
Keywords: High-voltage Lines Parallel Four-Circuit Lines Lightning Protection Lightning trip Trip-out rate
CLC: TM862
Type: Master's thesis
Year: 2011
Downloads: 68
Quote: 0
Read: Download Dissertation

Abstract


With power demand being continuously increased in our country, multi-circuittransmission line on the same tower is more widespread used. More electric power can betransmitted on multi-circuit transmission line, so it takes up a more important place in powersystem. The tower of multi-circuit transmission line, which is higher than the tower ofsingle-circuit transmission line, is more easily struck by lightning. Therefore, the problem oflightning protection is more serious and the study of lightning protection is even moreimportant. Recently, 220 kV four-circuit transmission line on the same tower and the voltagelevel which bellows it have been used widely in our country, whose performance of lightningprotection is recognized in operation. But 500 kV four-circuit transmission line on the sametower is developed in the preliminary stage, a great deal of problems exist and detailedcalculation and analysis is lacked for both performance of lightning protection andinfluencing factor. Therefore, it is essential to research this field.Lightning tipping on extra-high transmission line is mainly caused by shielding failureand back flashover. The calculation of them in regulations are only suited for single-circuittransmission line on low tower. For 500 kV four-circuit transmission line on the same tower,the calculation method in the regulations is not suited any more and the real lightningwithstand level of transmission line can not be calculated. Therefore, new model and methodmust be taken to calculate the performance of lightning protection for 500 kV four-circuittransmission line on the same tower.For 500kV four-circuit transmission line, two kinds of tower model are taken for examplebased on actual line. And calculation model of lightning protection suited for 500 kVfour-circuit transmission line is constructed, which can precisely reflect the process oflightning current transmitting on the tower. Based on ATP/EMTP, two kinds of model indifferent situation are analysed and calculated, and the performances of lightning protectionare found out. To ensure the accuracy of the calculation for shielding failure, the shieldingcontribution of shielding lines to phase conductor is considered, as well as the contributionbetween each line and the ground to phase conductors. In calculation of brake strikingperformance, multi-surge impedance model is used to describe the multi-circuit lines tower. Itis calculated particularly that the critical current required for back flashover of thismulti-circuit lines under different resistance values and phase conductors sequence. In orderto analyze improved solution for lightning protection of lines and provide guidance for designof projects, many means like changing types of tower head , changing phase conductors sequence, changing tower shielding lines bracket, changing shielding angle, increasingtriggering lightning rods are taken.

Related Dissertations

  1. Study on the Lightning Protection of the Regional Transmission Grid,TM862
  2. Research on Lightning Protection and Grounding Technique in Qinghai-Tibet Railway Transmission Line and Substation,TM862
  3. Study on the Simulation Model of Shielding Failure and the Lightning Protection Performance of Double Circuit for AC Transmission Line,TM862
  4. Investigations on the Electromagnetic Effects in Wind Turbines Struck by Lightning,TM862
  5. Reduce distribution network built mine clearance rate and arc reignition rate method,TM862
  6. Study on Calculation of Shielding Failure Flashover Rate for Transmission Line Based on Electric Geometry Model,TM862
  7. The Research on Lightning Protection of Transmission Lines in Luohe,TM862
  8. Research and Design Automatic Train Identification System,U284.48
  9. The Analysis and Application of Line MOA on AnHui 220kV Transmisson Line,TM862
  10. AutoCAD development of research in the substation lightning,TM862
  11. The Design of Luoshitan-Wuda 220kV Transmission Line and Study of Related Problems,TM726.1
  12. The Rating Design of Defending Thunder Device SPD Product,TM862
  13. Research on Lightning Protection and Grounding System in Qinghai-Tibet Railway Ge-La Segment,TM86
  14. Mountainous Area Transmission Line Lightning Protection Question Discussion,TM86
  15. A Studying the Design of Aolin 110kV Full-indoor GIS Transformer Substation,TM63
  16. Research on Lightning Protection of LV Device in Substation,TM862
  17. Investigation of Lightning Protection Performance of Yun-Guang ±800kV UHV DC Transmission Line,TM726
  18. Research of Lightning Over-Voltage in UHV Transmission Lines and Secondary Arc after the Single-Phase Trip-out Caused by Insulator-Flash,TM862
  19. Simulation of Transient in High Efficient Lightning-Protection Transformer,TM743
  20. Study on the Lightning Overvoltage Performance for 500kV Yafu Transmission Line in Guizhou,TM862
  21. High-rise building distribution systems and integrated lightning protection engineering research,TU85

CLC: > Industrial Technology > Electrotechnical > High Voltage Engineering > Overvoltage and Its Protection > Over-voltage protection devices
© 2012 www.DissertationTopic.Net  Mobile